Specifications of SS 4203 Gas Flow Computer

Functional
Flow Calculations AGA-3 1992/2000 orifice plate, V-Cone and AGA-7 turbine meter
Density Calculations AGA-8, 1992 and NX-19
Event/Alarm/History Logs 35 days hourly history, 35 days daily history, 700 events and 300 alarms (as per API 21.1)

Features
Protocols Modbus master/slave with store and forward
EFM (Enron) Modbus
Optional DNP 3
Discrete Input/Output One, dry contact, usable for level or pulse inputs to 10 kHz shared with 0.5 A sinking digital output
Turbine Meter Input One turbine meter input with integral pre-amplifier to 10 kHz shared with 0.5 A sinking digital output (DS version only)
Analog Inputs Two 0 to 5 V, 15-bit resolution (DS version only)
Analog Outputs Two 0 to 20 mA, sinking, 12-bit resolution (DR version only)
Communication Ports Two configurable RS-232/485 ports, 1200 to 115200 baud
Processors One 32-bit ARM microcontroller, 32 MHz clock
One sensor interface co-processor
Memory 4 Mb CMOS static RAM
8 Mb flash ROM (remotely downloadable)
1024 bytes EEPROM
Battery RAM memory and clock calendar retained for two years

Sensor Performance
Differential and Absolute Pressure Accuracy ±0.05% of span (for spans between 10% and 90% of URL)
Digital Output (spans <10% URL) Accuracy ±(0.005)x(URL/span)% of span*
Long Term Drift Stability <±0.05% of URL per year over five years
Temperature Accuracy Accuracy ±0.5°F (0.28°C), not including RTD uncertainties
Static Pressure Effect on Differential Pressure Readings The zero shift and span shift for a 1000 PSI (7 MPa) static pressure change is:
ZERO Shift ±0.05% of URL, SPAN Shift ±0.1% of reading
Ambient Temperature Effect Total effect for a 50°F (28°C) change within normal operating condition limits for absolute and differential pressure is:
Digital Output: ±(0.0625% URL + 0.125% Reading)

Power
Supply Requirements 9 to 30 Vdc, 330 mW typical at 12 Vdc

Certifications
c(CSA)us Explosion Proof, Class I, Division 1, Groups B, C and D Hazardous Locations
c(CSA)us Class I, Division 2, Groups A, B, C and D Hazardous Locations
IECEx to Exd IIC T6
ATEX to EEx d IIC T6
RTD connections rated non-incendive in Division 2 areas


*Accuracy stated includes the effects of linearity, hysteresis and repeatability.