SEARCH     
 

Specifications of the iESP™ Master Control Unit

Software Specifications
Control Two PID control loops, output calculated every second
Serial communication interface Two RS-232 asynchronous serial ports expandable up to four or six
Communications protocols Modbus ASCII, Modbus RTU or CAC 8500
Communications options Bell Model 103, 202 or 212 modem. Digital radio with integral modem (450- or 900-Mhz)

Hardware Specifications
Analog inputs Eight (one analog input can be jumpered for direct 100 Ohm platinum RTD input)
Range Nominal 0 to 5 Vdc, 1 to 5 Vdc, 0 to 25 mA or 4 to 20 mA (jumper selectable)
Resolution 12-Bit, unipolar
Accuracy Current inputs ±0.1% of full scale, voltage inputs ±0.1% of full scale (including linearity, hysteresis, repeatability, and resolution)
Temperature coefficient ±0.01% of full scale/degree F
Analog outputs Two
Range 0 to 25 mA or 4 to 20 mA
Resolution 12 Bit, unipolar
Accuracy ±1.1%, firmware calibratable to ±0.1% (including linearity, hysteresis, repeatability, and resolution)
Digital inputs Eight inputs @ 4 to 32 Vdc, 2 Hz maximum, 2 mA current limited (firmware filtered)
Optional Turbine meter prescaler accepts up to 5-Khz signals from turbine meter
Digital outputs Eight outputs @ 0.5-Amp continuous, 6 Amp pulsed, 32 Vdc maximum
Real time clock Accurate to within ±1 minute/ month over operating temperature range
Data ports Two RS-232 asynchronous serial ports (1 for MMI, 1 for 300 to 19.2 KBaud telecommunications)Expansion ports provide RS-232 or RS-485 interface to external instruments and/or controllers
Operating range -40° to +85°C, 0-95% relative humidity (non-condensing)
Overvoltage/transient protection All inputs/outputs and power supply devices provided with surge protection to ANSI/IEEE C37-90.1-1989 (IEEE Std. 472-1974)
Local display 2 x 24 LCD (-20°C to +70°C), optional with 20-key keypad
Power requirements 8 to 32 Vdc @ 2.5 Watts average
Options 110 Vac, 50/60-Hz input with one day battery (12-Vdc) backup, 0° to 60°C operation (assumes 1 Amp maximum load)
24 Vdc battery charging and backup for AC or solar powered units
12/24 Vdc DC to DC converter, used for 4 to 20 mA transmitters when battery backup is 12 Vdc
220 Vac, 50/60-Hz operation for AC input units
© 2011 Weatherford International Ltd.